RevPi as Modbus TCP Master

Introduction

This tutorial explains how to use a RevPi base module as a Modbus TCP Master to connect and communicate with slave devices. It provides step-by-step guidance to set up a RevPi system for industrial communication using the Modbus TCP protocol. This tutorial is designed for industrial automation professionals, IoT developers, and enthusiasts who want to configure and use Modbus TCP communication with Revolution Pi modules. Using the RevPi as a Modbus TCP Master is ideal for scenarios where devices such as sensors, actuators, or other industrial equipment need to be controlled or monitored in a networked environment.

Prerequisites

Hardware

  • RevPi base module
  • Slave device(s)
  • Matching cables with RJ45 connectors
  • Internet connection

Software

  • A modern web browser (e.g., Google Chrome or Mozilla Firefox).

System Setup

Ensure that:

  1. The RevPi base module and the slave devices are located on the same network.
  2. IP addresses of all slave devices are specified and documented as per the manufacturer's instructions.
  3. Each slave device has a unique IP address.

Step 1: Hardware Setup

▷ Connect the slave devices to the RevPi via the RJ45 jack.

▷ Note the IP addresses and ports of all slave devices.

Note:Avoid assigning the same IP address to multiple slave devices on the same port, as this will cause communication errors.

Step 2: Configure Modbus TCP Master in PiCtory

Start pictory.

Webstatus login

Add Base Module and Add the virtual Modbus TCP Master to your configuration.

  • Drag the base module from the Device Catalog onto the virtual DIN rail.

  • Open the folder Virtual Devices in the Device Catalog.

    • Drag Modbus TCP Master to the base module on the virtual DIN rail.
      ➜ The Modbus TCP Master will now appear in the configuration

pictory config

Configure Modbus TCP Master

  • Select the Modbus TCP Master in the configuration.

    ➜ In the Device Data window, optionally Assign appropriate I/O names for easier reference, e.g., 'Modbus_Input_1'

pictory config

▷ Open the Value Editor and configure the following parameters:

  • 'slave_IP_address': IP address of the Modbus TCP slave.
  • 'slave_tcp_port': Default is '502', as specified in the Modbus specification. This can be changed if required.

Save the configuration and restart the driver to apply the changes.

Step 3: Set Modbus Commands

  1. Open Extended Data
    ▷ Right-click the Modbus TCP Master in the configuration.

    ▷ Select Extended Data to open the command configuration interface.

  2. Add Modbus Commands
    ▷Configure the commands using the following parameters:

    • Unit ID: Refer to the slave's manual for this address. Use 255 if the slave ignores the address.
    • Function Code: Choose from the supported codes:
      • READ_COILS: Read single bits.
      • READ_DISCRETE_INPUTS: Read single input bits.
      • READ_HOLDING_REGISTERS: Read 16-bit registers.
      • READ_INPUT_REGISTERS: Read 16-bit input registers.
      • WRITE_SINGLE_COIL: Write a single bit.
      • WRITE_SINGLE_REGISTER: Write a whole register.
      • WRITE_MULTIPLE_COILS: Write consecutive bits.
      • WRITE_MULTIPLE_REGISTERS: Write consecutive registers.
    • Register Address: Define the Modbus register or bit address to access.
    • Quantity of Registers: Number of registers or bits to read/write.
    • Action Interval: Time interval in milliseconds for sending the command.
    • Device Value: Name of the variable in the RevPi process image.

    pictory config

Note: For devices using 0-based addressing, increment the register address by 1 during configuration.

  1. Save Configuration
    File > Save to save the settings.

    Tools > Reset Driver to activate the configuration

Step 4: Troubleshooting

If communication errors occur, check the Modbus_Master_Status register for error codes. Common codes include:

  • 0x10: Device not found (check wiring).
  • 0x11: Device does not respond or invalid register address.
  • 110: Connection timed out.
note
  • For further details, refer to the official Modbus specification.
  • Ensure proper wiring and configuration to minimize connection and communication issues.
  • To resolve errors:
    • Verify IP addresses and wiring.
    • Ensure no overlapping Modbus commands.

Modbus Master Task Management and Error Codes

The Modbus master can handle up to 32 tasks. Each task has a corresponding register for status and status reset. If an error occurs in a task, the error code is written to the Modbus register:
Modbus_Action_Status_[1…32].

The error remains in this register until the value 1 is manually written to the corresponding reset register:
Action_Status_Reset_[1…32].

The error codes correspond to the Modbus exception codes as defined in the Modbus specification.

Error Codes Table

The table below summarizes the most important error messages:

Error CodeNameDescription
1ILLEGAL FUNCTIONThe function code used is not allowed. Check if you are using the correct function code.
2ILLEGAL DATA ADDRESSThe Modbus register address used is not valid. The register is either write-protected or invalid. Check the register address.
3ILLEGAL DATA VALUEAt least one part of the data values used is invalid. For example, you may have entered too many registers. Check your values.
13INVALID DATAThe slave has answered an incomplete packet. This can happen after a connection interruption. Check your wiring.
110CONNECTION TIMED OUTThe slave did not respond fast enough or not at all. Check your configuration and wiring.

Example: Temperature Measurements with RevPi as Modbus TCP Master

Hardware Setup

The temperature sensor Inveo NANO TEMP serves as the Modbus slave in this example.

Configuration Details

Refer to the sensor's manual for the following data:

ParameterValue
IP Address192.168.0.103
Port502
Modbus Register4004
Modbus FunctionREAD_HOLDING_REGISTERS
Slave Address1

Define Modbus Commands

In the Extended Data interface, configure:

  • Slave Addr.: 1
  • Function Code: READ_HOLDING_REGISTERS
  • Register Addr.: 4004
  • Quantity of Registers: 1
  • Action Interval (ms): 1000
  • Device Value: Input_Word_1

pictory config

Query Data

  1. Save the configuration and reset the driver.
  2. Open a command line and run:
   piTest -r Input_Word_1

➜ You receive the data of your slave:

 2 Byte-Value of Input_Word_1: 284 dez (=011c hex)

The value 284 corresponds to 28.4 °C

Further Resources